About 75 kva Single Phase Pad Mounted Transformer
Evernew Transformer is committed to providing customized solutions for power needs. Our 75 kVA benchtop transformer not only meets and exceeds the DOE 2016 high efficiency standards, but also has passed CE, UL, cUL and other certifications to ensure product quality and safety. As one of the transformer manufacturers with the most UL and CUL certifications in the North American market, we supply thousands of transformers to various industries every year, including utilities, rural cities, photovoltaic power generation, traditional energy, data centers, digital currencies, and construction.
Our team has extensive transformer project experience and is proficient in international standards such as ANSI, IEEE, CSA, DOE, and NEMA. Whether you are located in the United States, Canada, Mexico, or other countries in South America, such as Argentina, Colombia, Brazil, etc., Evernew Transformer can provide you with customized services to meet specific project needs. We focus on providing the best transformer solutions based on our customers’ unique requirements to ensure the stable operation of your power system while optimizing energy efficiency and cost-effectiveness. Contact us to purchase a 75 KVA transformer now
Consult 75 KVA Transformer75 kVA Transformer Testing
At EverNew, every 75 kVA transformer undergoes a comprehensive series of routine tests before leaving the factory, strictly adhering to ANSI/IEEE C57.12.90、ANSI/IEEE C57.12.00 、IEC 60068standards. These tests are crucial for guaranteeing the performance and safety of the transformers. The routine tests include:
Ratio Test: Ensures the correct voltage ratio of primary to secondary windings.Ratio accuracy within ±0.5%.
Polarity Verification: Confirms the correct polarity of the transformer windings.Correct polarity configuration confirmed.
No-Load Loss Evaluation: Measures the power losses when the transformer is energized but not supplying any load.No-load losses corrected to 85°C, typically < 1% of rated power.
Excitation Current Measurement: Assesses the current required to energize the transformer at no load. Excitation current at 105% rated voltage, typically < 1% of rated current.
Load Loss and Impedance Measurement: Measures the power losses and impedance under full load conditions. Load losses corrected to 85°C, typically < 2% of rated power. Impedance within specified range, usually 2-5%.
Applied Voltage Test: Verifies the insulation integrity by applying a high voltage to the windings.Applied voltage typically 2-3 times the rated voltage for 1 minute without breakdown.
Induced Voltage Evaluation: Tests the transformer’s ability to withstand higher than normal operating voltages. Induced voltage typically 1.5 times the rated voltage for 60 seconds without breakdown.
Transformer Tank Leak Test: Ensures the tank is free from leaks.No detectable leaks under test conditions.
Temperature Rise Test: Measures the temperature rise under full load conditions.Temperature rise typically < 65°C over ambient temperature.
Insulation Resistance Test: Measures the resistance of the insulation system.Insulation resistance typically > 1,000 megaohms.
- Partial Discharge Test: Detects partial discharges to ensure insulation integrity.Partial discharge levels typically < 10 pC.
- Sound Level Test: Measures the sound levels emitted by the transformer. Sound levels typically < 60 dB(A) at 1 meter distance.
- Short-Circuit Withstand Test: Verifies the transformer’s ability to withstand short-circuit conditions.Transformer remains intact and operational after test.
- Impulse Test: Simulates lightning strikes and high-voltage surges.No insulation breakdown under impulse conditions, typically 5-10 times the rated voltage.
- Humidity and Environmental Tests: Exposes the transformer to various humidity and environmental conditions. No degradation in performance under test conditions.
- Mechanical Strength Test: Assesses the mechanical strength of the transformer’s components. Components withstand specified mechanical stresses without damage.
By implementing these rigorous testing procedures, EverNew ensures that each 75 kVA transformer meets the highest standards of quality and safety, providing reliable performance for our customers. If you need more information or advice on your transformer project, please feel free to contact us.
75 kVA Transformer Main Components
Accessory Name | Quantity | Accessory Name | Quantity |
---|---|---|---|
Nameplate | 1 | Ground shovel terminal | 2 |
Lifting bolts | 4 | Relief valve | 1 |
Hinge door | 1 | ELSP fuse | 1 |
Parking frame bracket | 1 | Cartridge fuse | 1 |
Flip top cover | 1 | Two-position LB switch | 2 |
Drain valve | 1 | Drip pan | 1 |
Oil level gauge | 1 | Processing | 2 |
Grounding strap copper | 1 | Tap changer | 1 |
Equipotential device | 1 | Filling plug | 1 |
High-voltage conduit well | 2 | Dust cap insert | 2 |
Low-voltage conduit | 3 | Grounding bracket | 1 |
Terminal clamp | 4 | Five-head bolt arrangement | 1 |
Technical Characteristics of 75 kVA Transformer
Place of Origin | China |
---|---|
Brand Name | Evernew Transformer |
Product Name | Oil Type Single Phase Transformer Pad Mounted |
Coil Number | 2 winding |
Coil Structure | TOROIDAL |
Product name | Pad mounted transformer |
Type | Loop Feed |
Rated capacity | 75 KVA(15 KVA- 333 KVA or Customized) |
Application | Mining |
Standard | IEC ANSI IEEE |
IEEE Standards | IEEE C57.12.00 |
Certification | UL Listed |
Efficiency | DOE 2016 Standard Compliant |
Temperature Rise | 65°C, 65/75°C, 75°C |
Frequency | 50/60Hz |
Material | Aluminum/Copper |
Cooling System | ONAN / KNAN |
Feed Type | Loop Feed / Radial Feed |
Primary voltage | 6kv-34.5kv or Customized |
Secondary voltage | 0.12KV-0.6KV or Customized |
Winding Configuration | Delta – Wye / Wye – Wye/ Delta – Delta/ Wye – Delta |
Tapping Range | ±2 x 2.5% |
Impedance | 4.35-5.75% |
Vector Group | As per requirement |
Type of Installation | Indoor / Outdoor |
Mounting | Pad-Mounted |
Warranty | 24 Months |
Customized | Accept |
Voltage Level of 75 kVA Single Phase Pad Mounted Transformer
Rated Power (KVA) | High Voltage (KV) | Low Voltage (V) | Standard | Loss (W) | |
---|---|---|---|---|---|
No-load Loss (W) | On-load Loss (W) | ||||
15KVA | 24.94kV/14.4kV 12.47kV/7.2kV 34.5KV/ 19.92KV/ 13.8KV/ 13.2KV/ or others | 120-240V 240-480V 347V 600V | IEEE/ ANSI/ DOE | 50 | 195 |
25KVA | 80 | 290 | |||
37.5KVA | 105 | 360 | |||
50KVA | 135 | 500 | |||
75KVA | 190 | 650 | |||
100KVA | 210 | 850 | |||
167KVA | 350 | 1410 |